IP Rating System |
The code letters IP of BS EN 60529:1989 refer to International Protection as applicable to enclosure or electrical equipment with a rated voltage not exceeding 72.5KV. The code and
rating system is composed by the two letters IP followed by two numbers:
the first one is the Code Number for dust protection (Numeral from 0 to
6), the second one is the Code Number for water protection (Numeral from 0
to 8) |
First Numeral: |
Second Numeral: |
||
Protection | Requirements | Protection | Requirements |
0 |
No protection |
0 |
No protection |
1 |
Full penetration of 50mm diameter sphere not allowed and shall have adequate clearance from hazardous parts. Contact with hazardous parts not permitted. |
1 |
Protected against vertical falling drops of water. Limited ingress permitted. |
2 |
Full penetration of 12.5mm diameter sphere not allowed. The jointed finger test shall have adequate clearance from hazardous parts |
2 |
Protected against falling drops of water with enclosure tilted 15° from the vertical. Limited ingress permitted. |
3 |
The access probe of 2.5mm diameter shall not penetrate. |
3 |
Protected against sprays to 60° from vertical. Limited ingress permitted. |
4 |
The access probe of 1.0mm diameter shall not penetrate |
4 |
Protected against water splash from all directions. Limited ingress permitted. |
5 |
Limited ingress of dust permitted (no harmful deposit) |
5 |
Protected against low pressure jets of water from all directions. Limited ingress permitted. |
6 |
Totally protected against ingress of dust |
6 |
Protected against strong jets of water |
7 |
Protected against the effects of immersion between 15cm and 1m |
||
8 |
Protected against longer periods of immersion under pressure |