IP Rating System

 

The code letters IP of BS EN 60529:1989 refer to International Protection as applicable to enclosure or electrical equipment with a rated voltage not exceeding 72.5KV.

The code and rating system is composed by the two letters IP followed by two numbers: the first one is the Code Number for dust protection (Numeral from 0 to 6), the second one is the Code Number for water protection (Numeral from 0 to 8)
 

             

 

First Numeral:
protection against ingress of solid foreign bodies

Second Numeral:
protection against harmful ingress of water

 Protection Requirements  Protection Requirements

0

No protection

0

No protection

1

Full penetration of 50mm diameter sphere not allowed and shall have adequate clearance from hazardous parts. Contact with hazardous parts not permitted.

1

Protected against vertical falling drops of water. Limited ingress permitted.

2

Full penetration of 12.5mm diameter sphere not allowed. The jointed finger test shall have adequate clearance from hazardous parts

2

Protected against falling drops of water with enclosure tilted 15° from the vertical. Limited ingress permitted.

3

The access probe of 2.5mm diameter shall not penetrate.

3

Protected against sprays to 60° from vertical. Limited ingress permitted.

4

The access probe of 1.0mm diameter shall not penetrate

4

Protected against water splash from all directions. Limited ingress permitted.

5

Limited ingress of dust permitted (no harmful deposit)

5

Protected against low pressure jets of water from all directions. Limited ingress permitted.

6

Totally protected against ingress of dust

6

Protected against strong jets of water

7

Protected against the effects of immersion between 15cm and 1m

8

Protected against longer periods of immersion under pressure

 

 

 

 Last update: April 2005